Owner's manual
5
Table 2-1 Log Input Mode Settings
Setup Item Selectable Items
(Selectable Range)
Description
Range Same as the DCV
range
Sets the range.
Span Lower Varies depending on the
input type
Sets the span lower limit.
Span Upper Varies depending on the
input type
Sets the span upper limit.
* Span Lower must be less than Span Upper.
Scale Lower 1.0E-15 to 1.0E+15 Sets the scale lower limit.
1.00E-15 to 1.00E+15 when the number of displayed
mantissa digits is 3.
Scale Upper 1.0E-15 to 1.0E+15 Sets the scale upper limit.
* 15 decades maximum.
* Scale Lower must be less than Scale Upper.
1.00E-15 to 1.00E+15 when the number of displayed
mantissa digits is 3.
Unit Up to 6 characters Sets the unit (alphanumeric characters).
2.2.2. Setting the Number of Displayed Mantissa Digits
1. Press MENU (switch to the setting mode).
2. Hold down FUNC for 3 s to switch to the basic setting mode.
3. Select Environment > Digits, Time indicate.
4. Set Digits to 2 or 3.
Setup Screen Example for the Number of Displayed Mantissa Digits (DX1000(N)
Example)