Owner's manual
93
Installation and Wiring
Recommended Replacement
Periods for Worn Parts
Setup Items and
Default Values
IM 04L42B01-02E
Communication (Serial) > Basic settings
Setup Item Selectable Range or Selections Default Value Setting
Without /AS1
Baud rate 1200/2400/4800/9600/19200/38400 9600
Data length 7/8 8
Parity Odd/Even/None Even
Handshaking Off:Off/XON:XON/XON:RS/CS:RS Off:Off
Address 1 to 99 1
Protocol Normal/Modbus/Modbus-M Normal
With /AS1
*3
The baud rate, data length, parity, handshaking, address items are the same as on a DX without the /AS1 option.
Protocol Normal/Modbus/Modbus-M/Barcode Normal
Communication (Serial) > Modbus master > Basic settings
Setup Item Selectable Range or Selections Default Value Setting
Read cycle 125ms/250ms/500ms/1s/2s/5s/10s 1s
Timeout 125ms/250ms/500ms/1s/2s/5s/10s/1min 1s
Retrials Off/1/2/3/4/5/10/20 1
Inter-block delay Off/5ms/10ms/15ms/45ms/100ms Off
Auto recovery Off/1min/2min/5min/10min/20min/30min/1h 2min
Communication (Serial) > Modbus master > Command settings
Setup Item Selectable Range or Selections Default Value Setting
Master command number 1-8/9-16 1-8
1 to 16
First
Last
Addr.
Regi.
Type
Off/R/R-M/W/W-M/E-M
*3
Depends on the command type.
Depends on the command type.
1 to 247
Numerical value
INT16/UINT16/INT32_B/INT32_L/UINT32_B/
UINT32_L/FLOAT_B/FLOAT_L
Off
–
–
1
30001
INT16
Communication (PROFIBUS-DP)
*2
Setup Item Selectable Range or Selections Default Value Setting
Node Address 0 to 125 3
Setup Items and Default Values