Setup Example 2: Flow Rate Measurement Channel and Alarm
DX2000
Flowmeter Channel 2
4 - 20 mA
Convert to 1-5 V with a shunt resistor
Setup Item Description Number in the Figure
Channel Use channel 2. 1
Tag FI-002 2
Input signal 1-5V 3
Input range 0.0 to 500.0 L/H 4
Alarm condition Output an alarm if the measured value is
less than or equal to 120.0 L/H.
Output destination: Relay contact (I03)
5
(1) Input Range and Alarm
Press MENU (to switch to setting mode).
Select the Menu tab > Meas Channel > Range, Alarm.
1
5
4
3
(2) Tag
Select the Menu tab > Meas Channel > Tag, Memory sample, Alarm delay.
2
Operation complete.
Setting the Input Range and Alarm