User Manual

IM 01E20F12-01E
3-1
3. GETTING STARTED
3. GETTING STARTED
Fieldbus is fully dependent upon digital communica-
tion protocol and differs in operation from conven-
tional 4 to 20 mA transmission and the BRAIN
communication protocol.
HMI
Class I Master
I/O CARD, PLC, etc.
PROFIBUS-DP
PROFIBUS-DP devices
PROFIBUS-PA devices (AXF)
PROFIBUS-PA (31.25 kbps)
Class 2 Master
FieldMate (FDT/DTM)
PDM (EDDL), etc.
DP/PA
Coupler
F0301.EPS
Figure 3.1 Profibus System Construction
3.1 Connection of Devices
The following are required for use with PROFIBUS
PA devices:
Power supply:
PROFIBUS PA requires a dedicated power supply.
It is recommended that current capacity be well over
the total value of the maximum current consumed
by all devices. Power is supplied by a DP/PA
coupler.
Terminators:
PROFIBUS PA requires two terminators. A termina-
tor shall be located at each end of the trunk cable.
•Field devices:
Connect PROFIBUS PA communication type AXF
(Refer to section 8.3 terminal connection). Two or
more AXF devices or other devices can be con-
nected.
DP/PA Couplers:
PROFIBUS PA requires DP/PA couplers which
convert the RS-485 signals to the IEC 61158-2
signal level and power the field devices via the
PROFIBUS PA.
•Cable:
Refer to Figure 3.1.
Table 3.1 PROFIBUS PA Cables and Transmissible Length
Ty pe A: Individually-shielded
twisted pair cable
Type of cable
#18AWG
(0.82 mm
2
)
Cable
specifications
1,900 m
Max. length of
cable
(reference value)
1,200 m
400 m
200 m
#22AWG
(0.32 mm
2
)
#26AWG
(0.13 mm
2
)
#16AWG
(1.25 mm
2
)
Ty pe B: Overall-shielded
twisted pair cable
Ty pe C: Unshielded twisted
pair cable
Ty pe D: Overall-shielded
non-twisted cable
T0401.EPS
Note: Yokogawa recommends the use of Type A.
Usage of Type B and D is restricted.
Yokogawa does not recommend the use of
Type C.
Before using a PROFIBUS PA configuration tool other
than the existing class 1 and class 2 Masters, confirm it
does not affect the loop functionality in which all
devices are already installed in operation. Disconnect
the relevant control loop from the bus if necessary.
IMPORTANT
It is mandatory to turn on the power supply of
the AXF before turning on the power supply for
the Profibus line.
Connecting a PROFIBUS PA configuration tool
to a loop with its existing class 1 and class 2
Masters may cause communication data
scrambling resulting in a functional disorder or
a system failure.