User Manual

IM 01E20F12-01E
9-9
9. PARAMETER LISTS
T0903-5.EPS
Index Parameter Valid Range Initial Value Description
Write
Mode
111 DISPLAY_SELECT1 This parameter is used in order to set the LCD display mode.Auto 1: Out Value0 to 4
112 DISPLAY_SELECT2 Auto 0: Off0 to 9
113 DISPLAY_SELECT3 Auto 0: Off0 to 9
114 DISPLAY_CYCLE Auto 1: 400ms This parameter is used in order to set the renewal cycle of LCD
display.
Renewal cycle: 200 msec “DISPLAY_CYCLE”
0: 200ms
1: 400ms
2: 1s,
3: 2s,
4: 4s,
5: 8s
115 LANGUAGE Auto 0: English0: English
116 RATE_LIMIT O/S 5 This parameter is used in order to set the rate limit value.0 to 10
117 DEAD_TIME O/S 0 This parameter is used in order to set the time for application of the
rate limit, and if a value of 0 is set, the rate limit function will be
terminated.
0 to 15
118 PULSING_FLOW O/S 0: No This parameter is used in order to set the pulsing flow support.0: No
1: Yes
119 POWER_SYNCH O/S 1: Yes
This parameter is used in order to indicate whether or not the
internal frequency is to be synchronized with that of the power supply.
0: No
1: Yes
120 POWER_FREQUENCY O/S 50
This parameter is used in order to set the power frequency.
47.00 to 63.00
121 SOFTWARE_REV_NO
This parameter is used to display the software revision number.
122 ADHESION_CHECK O/S 0: No
This parameter selects whether or not the adhesion diagnostic
function will be carried out.
NOTE
If the judgment value for Level 3 is exceeded, a warning is displayed;
and if the value for Level 4 is exceeded, an alarm is displayed.
0: No
1: Yes
123 ADHESION_LEVEL1 O/S 0.10
This parameter is used in order to set the resistance value for
judgment of Level 1.
0.00 to 100.00
124 ADHESION_LEVEL2 O/S 0.50
This parameter is used in order to set the resistance value for
judgment of Level 2.
0.00 to 100.00
125 ADHESION_LEVEL3 O/S 1.00
This parameter is used in order to set the resistance value for
judgment of Level 3.
0.00 to 100.00
126 ADHESION_LEVEL4 O/S 3.00
This parameter is used in order to set the resistance value for
judgment of Level 4.
0.00 to 100.00
127 ADH_MEASURE_VALUE
This parameter displays the value measured using the adhesion
diagnostic function.
0.00 to 1000.00