User Manual
IM 01E20F12-01E
9-6
9. PARAMETER LISTS
T0903-2.EPS
Index Parameter Valid Range Initial Value Description
Write
Mode
33 VOLUME_
FLOW
(DS-33)
Indicates the current measured value and status as the primary
value (volumetric flow).
This parameter is input to the AI Function Block and the Totalizer
Function Block.
Value
Value
–0
34 VOLUME_FLOW_UNITS This parameter is used in order to select the unit for VOLUME_
FLOW, VOLUME_FLOW_LO_LIMIT and VOLUME_FLOW_HI_
LIMIT parameters.
O/S See the “Unit”
sheet.
Specified at the
time of order
35 VOLUME_FLOW_LO_LIMIT This parameter is used in order to enter the lower range value for
volumetric flow.
O/S
-11.88 to 11.88 m/s
or -22.68 to 22.68 m/s
The value depends
on a volume flow unit.
Specified at the
time of order
36 VOLUME_FLOW_HI_LIMIT This parameter is used in order to enter the upper range value for
volumetric flow.
O/S
-11.88 to 11.88 m/s
or -22.68 to 22.68 m/s
The value depends
on a volume flow unit.
Specified at the
time of order
57 SAMPLING_
FREQ
(DS-33)
This parameter is used in order to indicates the field frequency of the
sensor (Sensor specific, must not be downloaded).
–75
58 SAMPLING_FREQ_UNITS This parameter is used in order to selected unit code for
SAMPLING_FREQ parameter.
O/S 1077: Hz 1077: Hz
69 VOLUME_FLOW_FTIME Setting of the damping time constant to VOLUME_FLOW.
The output to reach 63.2% from 0%.
O/S 0.1 to 200.0 3.0
70 DUAL_FREQUENCY_
MODE
Selection of excitation mode.
This parameter is effective when FLOW_TUBE is “ADMAG AXF”
and NOMINAL_SIZE is in between 25mm to 200mm.
Outside the field of that condition, the warning “71:Meas Mod Set”
will be displayed.
O/S 0: Standerd DF
1: Enhanced DF
0: Standard DF
71 LOW_MF This parameter is used in order to set the low-frequency meter factor.
This setting is linked with that of parameter CALIBR_FACTOR.
O/S 0.01 to 3.0000 1.0000
72 HIGH_MF This parameter is used in order to set the high-frequency meter
factor.
O/S 0.01 to 3.0000 1.0000
73 LOW_MF_EDF
This parameter is used in order to set the low-frequency meter factor
as required when Enhanced DF (i.e., enhanced dual frequency
excitation) is selected. If “Standard DF” has been selected for
Measure_Mode, neither Low_MF(EDF) nor High_MF(EDF) is
displayed.
O/S 0 to 3.0000 1.0000
74 HIGH_MF_EDF This parameter is used in order to set the high-frequency meter
factor as required when Enhanced DF (i.e., enhanced dual
frequency excitation) is selected.
O/S 0 to 3.0000 1.0000
75 SELECT_FLOW_TUBE This parameter is used in order to set the types of flow tube.
When combining this product with an AXF Remote Flow tube,
“ADMAG AXF” should be selected.
O/S 0: ADMAG AXF
1: ADMAG
2: ADMAG AE
3: ADMAG SE
4: YEWMAG
5: Calibrator
6: Other
0: ADMAG
AXF
76 DENSITY_UNIT This parameter selects the units for density as required when making
settings using Mass_Density.
O/S 1097: kg/m
3
1108: lb/gal
1107: lb/cf
1097: kg/m
3
59-68 reserved by PNO
Status – Good
Status – Good
32 O/SNOMINAL_SIZE_UNITS
Specified at the
time of order
1013: mm
1019: inch
This parameter is used in order to select the unit of size (diameter)
of the sensor (flow tube).