User Manual

IM 01E20F02-01E
6-2
Table 6.1 Status of each parameter in failure mode (1/2)
System
Alarms
10:uP Fault Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Device Failure,
Const.
Bad;
Device Failure,
ok
Bad;
Device Failure,
ok
Uncertain
Non Specific,
ok
Uncertain; Last
Usable Value,
Const.
Uncertain
Non Specific,
ok
Uncertain; Last
Usable Value,
Const.
Uncertain
Non Specific,
ok
Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Device Failure,
Const.
Bad;
Device Failure,
Const.
Bad;
Device Failure,
Const.
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault
15:Coil Open
16:EEPROM Dflt
100:Comm uP
Fault
101:Comm
EEPROM Fault
102:Total1 Not
Saved
103:Total2 Not
Saved
104:Total3 Not
Saved
–––––– ––
Good;
Active Critical
Alarm, Low limt.
Good;
Active Critical
Alarm, Low limt.
Good;
Active Critical
Alarm, Low limt.
––
105:Comm Error1
Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Device Failure,
ok
Uncertain
Non Specific,
ok
Uncertain; Last
Usable Value,
Const.
Uncertain
Non Specific,
ok
Uncertain
Non Specific,
ok
Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Device Failure,
ok
106:Comm Error2
107:DL Incomplete
30:Sig Overflow
Process
Alarms
Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Sensor Failure,
Const.
Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Sensor Failure,
Const.
Bad;
Sensor Failure,
Const.
Bad;
Sensor Failure,
Const.
Uncertain; Last
Usable Value,
Const.
Uncertain
Non Specific,
ok
Uncertain
Non Specific,
ok
TOT1: Good; Active
Critical Alarm, Low limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Critical Alarm, Low limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Critical Alarm, Low limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Critical Alarm, High limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Critical Alarm, High limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Critical Alarm, High limt.
TOT2: --
TOT3: --
Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Sensor Failure,
Const.
Uncertain;
Substitude Value,
ok
Uncertain;
Last Usage Value,
ok
Bad;
Sensor Failure,
Const.
31:Empty Pipe
33:Adhesion Alm
34:Insulation Alm
32:HH/LL Alm
110:AI Lo Lo Alm
111:AI Hi Hi Alm
Good;
Active Critical
Alarm, High limt.
Good;
Active Critical
Alarm, High limt.
Good;
Active Critical
Alarm, High limt.
AI Lo Alm
Good;
Active Advisory
Alarm, Low limt.
Good;
Active Advisory
Alarm, Low limt.
Good;
Active Advisory
Alarm, Low limt.
AI Hi Alm
Total1 Lo Lo Alm
Total1 Hi Hi Alm
TOT1: Good; Active
Advisory Alarm,Low limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Advisory Alarm,Low limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Advisory Alarm,Low limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Advisory Alarm,High limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Advisory Alarm,High limt.
TOT2: --
TOT3: --
TOT1: Good; Active
Advisory Alarm,High limt.
TOT2: --
TOT3: --
TOT1: --
TOT2: Good; Active
Critical Alarm, Low limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Critical Alarm, Low limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Critical Alarm, Low limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Critical Alarm, High limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Critical Alarm, High limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Critical Alarm, High limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Advisory Alarm,Low limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Advisory Alarm,Low limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Advisory Alarm,Low limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Advisory Alarm,High limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Advisory Alarm,High limt.
TOT3: --
TOT1: --
TOT2: Good; Active
Advisory Alarm,High limt.
TOT3: --
TOT1: --
TOT2: --
TOT3: Good; Active
Critical Alarm, Low limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Critical Alarm, Low limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Critical Alarm, Low limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Critical Alarm, High limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Critical Alarm, High limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Critical Alarm, High limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Advisory Alarm,Low limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Advisory Alarm,Low limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Advisory Alarm,Low limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Advisory Alarm,High limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Advisory Alarm,High limt.
TOT1: --
TOT2: --
TOT3: Good; Active
Advisory Alarm,High limt.
Total1 Lo Alm
Total1 Hi Alm
Total2 Lo Lo Alm
Total2 Hi Hi Alm
Total2 Lo Alm
Total2 Hi Alm
Total3 Lo Lo Alm
Total3 Hi Hi Alm
Total3 Lo Alm
Total3 Hi Alm
Good;
Active Advisory
Alarm, High limt.
Good;
Active Advisory
Alarm, High limt.
Good;
Active Advisory
Alarm, High limt.
––
–––
–––
–––––– ––
108:Download Fail
Category Alarm
FSAFE_TYPE = 0
AI Block
FSAFE_TYPE = 1 FSAFE_TYPE = 2 FAIL_TOT = 0 FAIL_TOT = 1 FAIL_TOT = 2
TOT Block
FSAFE_TYPE = 0
DI Block
FSAFE_TYPE = 1 FSAFE_TYPE = 2