Manual
Table Of Contents
- Contents
- 1. INTRODUCTION
- 2. HANDLING PRECAUTIONS
- 3. INSTALLATION
- 4. WIRING
- 5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)
- 6. PARAMETER DESCRIPTION
- 6.1 Parameters
- 6.2 Parameter Lists
- 6.3 Parameter List Overview
- 6.4 Parameter Description
- (1) Menu B: Easy Setup items
- (2) Menu C: Basic Setting items
- (3) Menu D: Total Setting items
- (4) Menu E: Pulse Setting items
- (5) Menu F: Status Functions Setting items
- (6) Menu G: Alarm Setting items
- (7) Menu H: Display Setting items
- (8) Menu J: Auxiliary Function Setting items
- (9) Menu K: Diagnostic Function Setting items
- (10) Menu M: Automatic Zero AdjustmentFunction Setting items
- (11) Menu N: Loop Test Setting items
- (12) Menu P: Parameter Protection items
- 6.5 Alarm Functions
- 7. OPERATION VIA BRAIN TERMINAL (BT200)
- 8. OPERATION VIA HART COMMUNICATOR TOOL (HART 5)
- 9. ACTUAL OPERATION
- 10. MAINTENANCE
- 11. OUTLINE
- REVISION RECORD

IM 01E20C01-01E
6-2
6. PARAMETER DESCRIPTION
6.3 Parameter List Overview
(1) Item A (Menu A): Display items
Menu A contains the instantaneous flow rate, totalization values, and other items relevant to display.
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
T0602.EPS
A00
A10
A20
A21
A30
A31
A32
A60
Display
(DISPLAY)
FR
(FLOW RATE (%))
FR
(FLOW RATE)
FR
(FLW RATE (mA))
FTL
(TOTAL)
RTL
(REV TOTAL)
DTL
(DIF TOTAL)
—
(SELF CHECK)
For Display Mode only
For Display Mode only
For Display Mode only
For Display Mode only
For Display Mode only
For Display Mode only
See “6.5 Alarm Functions”.
-110.0 to 110.0
-999999 to 999999
2.400 to 21.600
0 to 99999999
0 to 99999999
-99999999
to 99999999
Good
Error
R
R
R
R
R
R
R
%
B21/B22
(C40/C41)
mA
B30
(D10)
B30
(D10)
B30
(D10)
1
0 to 3
3
0 to 7
0 to 7
0 to 7
(2) Item B (Menu B): Easy Setup items
Those parameters with a high frequency of use have been grouped together in Menu B. All basic functions can be
controlled using only the parameters from this block.
T0603-1.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
B00 Easy Setup
(EASY SETUP)
B10 Language
(LANGUAGE)
W English
Japanese
French
German
Italian
Spanish
English Selects the language used for the
display unit. Linked with H30.
B21 Base Flow Unit
(FLOW UNIT)
W Ml(Megaliter)
m
3
kl (Kiloliter)
l (Liter)
cm
3
m
t
kg
g
kcf
cf
mcf
Mgal (US)
kgal (US)
gal (US)
mgal (US)
kbbl (US Oil)
bbl (US Oil)
mbbl (US Oil)
ubbl (US Oil)
kbbl (US Beer)
bbl (US Beer)
mbbl (US Beer)
ubbl (US Beer)
ft
klb (US)
lb (US)
m (*) Selects flow units for the flow
rate span. Linked with C40.
B20 Flow Damping
(FLOW DAMPING)
W 0.1 to 200.0 s 1 3.0 s Sets damping time. Linked with
C11.