Manual

IM 1E10C1-E
11-9
11. PARAMETER LIST
Line size 0.01 to 300.0 mm/inch 100.0 W Sets flow tube nominal size in selected unit. b07
PV Damp 0.05 to 200.0 sec. 3.0 W Sets damping time constant of output. b02
Tag Enter characters W Sets tag no. up to 8 characters.
Descriptor Enter characters W Sets user-defined characters up to 16.
Message Enter characters W Sets user-defined characters up to 32.
Date 01/01/00 to 12/31/99 0 W Sets month/day/year.
Base bol unit (00) k Cum m W Selects volume unit of flow span. b04
(01) Cum
(02) L
(03) Cucm
(04) M gal
(05) k gal
(06) gal
(07) m gal
(08) k bbl
(09) bbl
(10) m bbl
(11) u bbl
(12) m
(13) ft
Base time unit (00) d s W Selects time unit of flow span. b05
(01) h
(02) min
(03) s
Velocity check 0 to 32.767 m/s R Displays span in m/s. b13
Size unit (00) mm mm W Selects flow tube nominal size unit. b06
(01) in
MF 0.2500 to 3.0000 1.0000 W Sets meter factor. b08
(Actual flow test data has been entered.)
Flow dir (00) Forward Forward W Selects flow direction. b14
(01) Reverse
PV % rnge –110.0 to 110.0% R Displays instantaneous flow rate in %. A10
Rate limit 0 to 10% 5 W Sets the level to reduce output fluctuation. n03
Dead time 0 to 15 sec 0 W Sets the dead time to reduce output fluctuation. When “0” is set, n04
“Rate limit” is not available.
Power synch (00) Yes Yes W Selects synchronization between excitation frequency and n05
(01) No power frequency.
Power freq 47.00 to 63.00 Hz 50.00 W Sets AC power frequency for DC power supply. b12
Total unit (00) n UNIT/P PULSE/s W Selects totalization rate unit. E01
(01) u UNIT/P (“UNIT” in the selection on the left represents the “Base vol
(02) m UNIT/P unit” selected.)
(03) UNIT/P
(04) k UNIT/P
(05) M UNIT/P
(06) PULSE/s
Total scale 0.0000 to 30000 0 W Sets totalization rate. E02
Total low cut 0 to 100% 3 W Sets low cut width of totalization. E03
Name Data Range, Units
Default
Value
R/W Description
Indicator
of SE