User Manual

<C3. Requirements for Installation>
C3-1
IM 01W02E01-01EN
C3. Requirements for Installation
C3.1 Requirements for Installation Locations
The installation of YFGW510 and eld wireless devices must meet the following conditions:
The eld wireless equipment should be mounted in the place where no obstacle exists
around the antenna. Especially, YFGW510 should be mounted in the condition that no ob-
stacle exists around the antenna.
If there is a pipe for mounting or plumbing in the direction except for the communication
partners, the antenna should be more than 30 cm apart from them.
When the wireless LAN antenna or wirelesseld antenna do not meet above requirements,
use an extension cable to place the antenna where radio waves will not be affected by ob-
stacles.
All antennas must be in the upright position.
The antenna of eld wireless equipment must be installed at least 1.5 meter above the
ground (oor)
The YFGW510 should be installed at a location as close as possible to the center of the eld
wireless network.
Ensure that the eld wireless devices that are located within the wireless communication
range are within the line of sight of each other. In the star topology, the YFGW510 must
meet this condition.