User Manual
<C1. Installation Environment>
C1-1
IM 01W02E01-01EN
PART-C. INSTALLATION
This section describes installation for YFGW510.
Follow the steps below to install YFGW510.
1. Installation of YFGW510
2. Wiring of the power supply, grounding cable, signal cables and mounting/wiring of
antenna(s)
C1. Installation Environment
YFGW510 should be installed in appropriate conditions to ensure its stable operation.
The table below shows details of the installation environment for YFGW510.
Item Environment Note
Power supply
Rated voltage 24 V DC
Voltage range 10 to 26.4 V DC
Momentary power
failure
1 ms or less (instant
disconnection)
Ripple ratio 1%p-p or less
Terminal M4 screw terminal (power supply and ground)
Maximum power consumption 3.5 W
Grounding
Class D grounding (100 ohms or less) No sharing with other
devices
Temperature
range
Operating -40 to 65°C
Transport/storage -40 to 85°C
Humidity
range
Operating 0 to 100% RH (No condensation)
Transport/storage 0 to 100% RH (No condensation)
Temperature
gradient
Operating ±10°C/h or less JEIDA29 class B
Transport/storage ±20°C/h or less
Protection degree IP66 IEC529
Vibration resistance
Displacement amplitude: 0.21 mm (10 to 60 Hz)
Acceleration amplitude: 3 G (60 to 2000 Hz)
Shock resistance
50 G 11 ms (de-energized, with half-sine wave
pulse in three directions)
IEC68-2-27
Altitude 3000 m or less
Noise
resistance
Electric eld 3 V/m or less (80 MHz to 1 GHz)
Electrostatic
discharge
4 kV or less (contact discharge), 8 kV or less
(aerial discharge)
Cooling Natural air cooling
Mounting 2-inch pipe With dedicated brackets
IMPORTANT
• Avoid direct sunlight.
• Keep away conductive particles such as iron and carbon.
• Avoid corrosive gases such as hydrogen sulde, sulfurous acid, chlorine and ammonia.