User Manual Part 2

Link CX-24 User’s Manual
Version 1.0 Page 38 February 2004
Table 2.6 – Electrical Connection Checklist
Checklist Item Verified Inspector Date
Is the proper voltage supplied to the Link CX-24
(PWR/LCL ALM LED on)?
Is the Link CX-24 receiving signal from the radio link
(RF LINK LED on)?
When the Link CX-24 is connected to DS-3 or
equipment, is the Link CX-24 receiving the expected
signal
(DATA LED on)?
When the Link CX-24 is connected to Ethernet
equipment on port ETHERNET 1, is the Link CX-24
receiving the expected signal (ENET 1 LED on or
flashing)?
When the Link CX-24 is connected to Ethernet
equipment on port ETHERNET 2, is the Link CX-24
receiving the expected signal (ENET 2 LED on or
flashing)?
The next series of acceptance tests requires you to log in to the built-in web server with a computer
equipped with a web browser.
52 Connect your computer to the Link CX-24 through the Ethernet equipment connected to the
ETHERNET 1 or ETHERNET 2 port.
53 Log in to the Link CX-24 built-in web server to display the Monitor page as described in Section
2.10.2.
54 Make sure the Automatic Tx Power Control indicated in the lower half of the Monitor page is set to
Disabled.
55 Record the RSSI indicated at the top of the Monitor page. Save this number for later troubleshooting.
56 If you are acceptance testing DS-3 versions of the Link CX-24, continue with Step 57. If you are
acceptance testing Ethernet versions of the Link CX-24, continue with Step 58.
Testing DS-3 Link CX-24s
57 Go to the Test page and verify that the Link CX-24 passes the tests in Table 2.7.

Summary of content (44 pages)