Operating instructions
12
WATER QUALITY
It is the Owner/End User’s responsibility to 
have the cooling water analyzed and chemically
treated (as often as necessary) so that it 
conforms to the limits specified in Table 1. The
water quality in the chilled/hot water, cooling
water, and heat medium circuits shall not 
exceed the following limits:
ITEM
pH (at 77
o
F)
Conductivity (µS/cm at 77
o
F)
Chloride ion (Cl
-
ppm)
Sulfate ion (SO
4
2-
ppm)
M-alkalinity (CaCO
3
ppm)
Total hardness (CaCO
3
ppm)
Calcium hardness (CaCO
3
ppm)
Ionic Silica (SiO
2
ppm)
Total iron (Fe ppm)
Copper (Cu ppm)
Sulfide ion (S
2-
ppm)
Ammonium ion (NH
4
+
ppm)
Residual chlorine (Cl ppm)
Free carbon dioxide (CO
2
ppm)
Ryzner stability index
Standard
Reference
CHILLED/
HOT
WATER
6.8 - 8.0
400
50
50
50
70
50
30
1.0
1.0
ND
1.0
0.3
4.0
HEAT
MEDIUM
7.0 - 8.0
300
30
30
50
70
50
30
1.0
1.0
ND
0.1
0.1
0.4
COOLING
WATER
6.5 - 8.2
800
200
200
100
200*
150
50
1.0
0.3
ND
1.0
0.3
4.0
6.0 - 7.0
MAKE-UP
WATER
6.8 - 8.0
300
50
50
50
70
50
30
0.3
0.1
ND
0.1
0.3
4.0
NOTES:
1.  ND (Not Detectable)
2.  *Maximum total hardness of make-up water shall not exceed 70 ppm when bleed off is the only
method used to control water quality.
Table 1 WATER QUALITY REQUIREMENTS
TROUBLESHOOTING GUIDE
SYMPTOM: Chiller/chiller-heater does not operate
POSSIBLE CAUSE REMEDY
Power supply is disconnected
Check the power  ON  lamp. If it is  OFF  check that the main 
disconnect is closed and the line fuses are in good condition.
Solution pump overload
Check for Error Code E08 on the control panel. If this error code is
relay tripped 
displayed, first push the manual Reset button on the overload relay
and then push the Alarm Reset on the control panel. 
Manual reset device is tripped
Check the Error Code on the control panel and identify the fault
from Table 2. After the cause is eliminated, push the Alarm Reset. 
High heat medium inlet 
Check for Error Code E38 on the control panel. If this error code is
temperature 
displayed, push the Alarm Reset on the control panel after the heat
medium inlet temperature falls below 190.4
o
F.
Fuse has melted
Check the condition of each fuse in the control box and replace as
necessary.