Instruction manual

Error Codes
99
01H
02H
03H
21H
22H
Error Code
Contents
Function code error
Function code from PLC is other than 03H, 08H or 10H.
Improper register number
No register numbers to be accessed have been registered.
ENTER command 0900H that is an exclusive-use register for
write-in was read out.
Improper quantity
The number of data items to be read or write-in is not in the
range between 1 and 16.
The number of data items in a message is not the value obtained
by multiplying the quantity by two in the write-in mode.
Data setting error
A simple upper/lower limit error occurred with control data or
constant write-in.
A constant setting error occurred when a constant was written.
Write-in mode error
Attempt to write-in a constant from PLC was made during running.
Attempt to write-in an ENTER command from PLC was made
during running.
Attempt to write-in a constant from PLC was made during UV
occurrence.
Attempt to write-in an ENTER command from PLC was made
during UV occurrence.
Attempt to write-in a constant other than n001=12, 13
(constant initialization) from PLC was made during F04 occurrence.
Attempt to write-in a constant from PLC was made while data
were being stored.
Attempt to write-in data exclusive for read-out from PLC was made.
* Refer to the constants list for constants that can be changed during operation.
VS-606V7 is 100,000; do not execute the ENTER command excessively.
When a constant is changed from the digital operator, the constant data
on the RAM is written to the non-volatile memory without ENTER
command.
Register number 0900H is used only for write-in. If this register is read-
out, register number error (error code: 02H) occurs.