Instruction manual

Storing constants [ENTER command] (can be written only.)
98
Register
Number
Name
Contents
Setting
Range
Default
0900H
ENTER
command
Write in constant data to
non- volatile memory
(EEPROM).
0000H to
FFFFH
---
When a constant is written from the PLC by communications, the
constant is written to the constant data area on the RAM in the VS-
606V7. ENTER command is a command to write the constant data on
the RAM to the non-volatile memory in the VS-606V7. Writing data
(can be undefined) to register number 0900H during stop executes this
ENTER command.
Maximum number of writing times of the non-volatile memory used for
Register No. bit
002DH
002FH-0030H
003DH
Reserved
1 P1 ON
0 CRC error
1 P1 ON
2 P2 ON
2 (Not used)
3 Parity error
4 Overrun error
Communications error
5 Framing error
6 Timeover
7 (Not used)
0031H Main circuit DC voltage (1 / 1V)
0032H Torque monitor (1 / 1%; 100% / Motor rated torque ; with sign)
003EH-00FFH Reserved
3 - F (Not used)
Description
1 :
ON
0 :
OFF
0 :
OFF
0 :
OFF
1 :
ON
1 :
ON
0033H-0036H (Not used)
0037H Output Power (1/1W : with sign)
0038H
PID feedback value (100% / Input equivalent to max. output frequency; 10 / 1%; without sign)
0039H
PID input value (±100% / ± Max. output frequency ; 10/1%; with sign)
003AH
PID output value (±100% / ± Max. output frequency ; 10/1%; with sign)
003BH-003CH Reserved
Multi-function
output
0 MA
1: Frequency reference loss
Inverter
status
002EH
0 Frequency reference loss
1-F (Not used)
*
Communications error contents are saved until fault reset is input.
(Reset is
enabled during run
.
)