Register No. bit
002CH
Inverter status
0 Run
1 Zero - speed
2 Frequency agreed
3 Minor fault (Alarm is indicated)
4 Frequency detection 1
5 Frequency detection 2
6
7 Undervoltage detection
8 Baseblock
9 Frequency reference mode
A Run command mode
B Overtorque detection
C
D Fault restart
E Fault (Including MEMOBUS communications timeover)
F MEMOBUS communications timeover 1 : timeover
Description
1 : Ready
1 : Undervoltage detection
1 : Inverter output baseblock
1 : Other than communications
0 : Communications
1 : Other than communications
0 : Communications
1 : Detection or overtorque fault
1 : Fault
1 : Output frequency (n095)
1 : Output frequency (n095)
1 : Agreed
1 : Zero - speed
1 : Run
Inverter operation ready
Undertorque detection 1 :
Detection or undertorque
fault
Terminal S4 1 : Closed
Terminal S5 1 : Closed
Terminal S6 1 : Closed
1 : Closed
Sequence input status
0
Terminal S1 1 : Closed
1 : Closed
1 : Closed
Terminal S2
Terminal S3
0 : Open
0 : Open
0 : Open
0 : Open
0 : Open
0 : Open
6 Terminal S7
(Not used)
002BH
1
2
3
4
5
7 - F
0 : Open
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Operator function stop (STP)
Sequence error (SER)
Simultaneous FWD/REV run commands (EF)
External baseblock (BB)
Overtorque detection (OL3)
Cooling fan overheat (OH)
Main circuit overvoltage (OV)
Main circuit undervoltage (UV)
Cooling fan fault (FAN)
Communications fault (CE)
Option card communications error (BUS)
Undertorque (UL3)
Inverter overheat alert (OH3)
PID feedback loss (FBL)
Emergency stop (STP)
Communications waiting (CAL)
002AH
Alarm description