Instruction manual

95
Data
Reference Data (available to read out / write in)
Note : Write in 0 for unused bit. Never write in data for the reserved register.
Simultaneous Broadcasting Data (available only for write in)
Bit signals not defined as the broadcast operation signals are used as the local
station data signals.
Register No. bit
0000H
0001H
Reserved
Reserved
0 Run command 1 : Run 0 : Stop
1 Reverse run 1 : Reverse run 0 : Forward run
2 External fault 1 : Fault (EFO)
3 Fault reset 1 : Reset command
4 Multi-function input reference 1 (Function selected by n050)
5 Multi-function input reference 2 (Function selected by n051)
6 Multi-function input reference 3 (Function selected by n052)
7 Multi-function input reference 4 (Function selected by n053)
8 Multi-function input reference 5 (Function selected by n054)
9 Multi-function input reference 6 (Function selected by n055)
A Multi-function input reference 7 (Function selected by n056)
B - F
0002H Frequency reference (unit : n152)
0
Multi-function output reference 1
(Effective when n057=18)
( 1 : MA ON 0 : MA OFF )
1
Multi-function output reference 2
(Effective when n058=18)
( 1 : P1 ON 0 : P1 OFF )
2
Multi-function output reference 3
(Effective when n059=18)
( 1 : P2 ON 0 : P2 OFF )
3 - F
0003H
0009H
0004H-
0008H
Reserved
000AH-
001FH
V / f gain (1000 / 100%) Setting range : 2.0 to 200.0%
(Not used)
(Not used)
Description
4 External fault 1 : Fault (EFO)
5 Fault reset 1 : Fault reset command
Register No. bit
0001H
0002H
0 Run command 1 : Run 0 : Stop
1 Reverse run 1 : Reverse run 0 : Forward run
2 (Not used)
3 (Not used)
6 - F (Not used)
30000 / 100% fixed unit
(Data is converted into 0.01 Hz inside the inverter, and fractions are
rounded off.)
Description