Instruction manual

Selecting Cooling Fan Operation
In order to increase lifetime, the cooling fan can be set to operate only when
inverter is running.
n039 = 0 (Initial setting) : Operates only when inverter is running
(Continues operation for 1 minute after
inverter is stopped.)
= 1 : Operates with power ON
Using MEMOBUS (MODBUS) Communications
Serial communication is available with VS-606V7 using programmable controller
(MEMOCON series) and MEMOBUS. Refer to MEMOBUS Instruction Manual
(Manual No.: TOEZ-C736-70.1) for details of communications.
MEMOBUS (MODBUS) communications
MEMOBUS system is composed of a single master (PLC) and slaves (1
to 31 VS-606V7 units).
Communication between master and slave (serial communication) is
controlled according to the master program with the master initiating
communication and the slave responding.
The master sends a signal to one slave at a time. Each slave has a pre-
registered address No., and the master specifies the number and conduct
signal communications. The slave receives the communications to carry
out designated functions and reply to the master.
Communications specifications
89
MEMOCON Series
Example of RS-485
communication
VS-606V7 VS-606V7 VS-606V7
Interface
Synchronization
Communication
parameters
Communication
protocol
Max. number of
inverters that can be
connected
RS-422, RS-485
Asynchronous (Start-stop synchronization)
Baud rate : Selected from 2400/4800/9600/19200 bps
Data length : 8bit fixed
Parity : Selected from even/odd/none
Stop bits : 1bit fixed
MEMOBUS (MODBUS) (RTU mode only)
31 units (When using RS-485)