Setting
0
1
Provided
Not Provided (when braking
resistor mounted)
Stall prevention during
deceleration
SET
DECEL
TIME
TIME
Controls the deceleration
time to prevent overvoltage
fault.
FREQUENCY
Stall prevention during deceleration (n092)
To prevent overvoltage during deceleration, the inverter automatically
extends the deceleration time according to the value of main circuit DC
voltage. When using an optional braking resistor, set n092 to 1.
Setting
0
1
Contest
No.
Setting
Range
Accel/decel time
selection during stall
prevention
Initial
Setting
Function
The stall prevention level becomes the level set for the constant n094 in
all frequency areas.
The following shows that the stall prevention level is automatically
decreased in the constant output range (Max. frequency>Max.
voltage output frequency).
The lower limit is 40% of the set value of n094.
Accel/decel time selection during stall prevention (n116)
With this function, acceleration/deceleration time when moving to
prevent stalling during operations can be assigned to the two constants,
n021 and n022.
n116
Setting Function
0
1
Accel / decel time is set by accel / decel time 1 or 2.
Accel/decel time is fixed at accel/decel time 2(n021, n022)
0
Name
Unit
-
0 = Disabled
1 = Enabled
n116 Setting
n115 Setting
max. voltage output frequency n013
output frequency
Operation level
Constant output area
Operation level =
n094 x
Lower limit
n094
40% of n094
n013
Output frequency