Analog input level
77
1 Auxiliary frequency reference (n077=1)
100%=Max. output frequency(n011)
FREF2
100%
0%
0V
(4mA)
10V
(20mA)
2 Frequency reference gain (n077=2)
FGAIN
2.00
1.00
0
0V
(4mA)
5V 10V
(20mA)
4 Output voltage bias (n077=4)
The VBIAS value to be added is doubled
for 400V class inverters.
VBIAS
100%
0%
0V
(4mA)
10V
(20mA)
3 Frequence reference bias (n077=3)
FBIAS
n079
-n079
0%
0V
(4mA)
10V
(20mA)
5V
Constant
No.
n078
Name Unit
Setting
Range
Initial
Setting
Multi-function analog
input signal selection
0= Digital operator terminal
(voltage: 0 to 10V)
1= Digital operator terminal
(current 4 to 20mA)
10
Multi-function analog input signal selection (n078)
Constant
No.
n079
Name Unit
Setting
Range
Initial
Setting
Frequency reference
bias setting
0 to 50
100% /
Max. output frequency
(n011)
%10
Frequency reference bias setting (n079)