Instruction manual

75
Notes :
1. When UP/DOWN command is selected, the upper limit speed is set regardless of frequency
reference.
Upper limit speed = Maximum output frequency (n011)
Frequency reference upper limit (n033)/100
2. Lower limit value is either minimum output frequency (n016) or frequency reference lower
limit (n034) (whichever is larger.).
3. When the FWD (REV) run command is input, operation starts at the lower limit speed
without an UP/DOWN command.
4. If the jog command is input while running by the UP/DOWN command, the jog command
has priority.
5. Multi-step speed reference 1 to 4 is not effective when UP/DOWN command is selected.
Multi-step speed reference is effective during running in hold status.
6. When 1 is set for HOLD output frequency memory selection (n100), output frequency can
be recorded during HOLD.
Setting
Description
Setting
0
1
Output frequency is not recorded during HOLD.
When HOLD status is continued for 5 seconds or longer, the output
frequency during HOLD is recorded and the inverter restarts at
the recorded frequency.
Communication/multi-function input terminal selection input (setting: 18)
Operation can be changed from communication command, or from multi-
function input terminal or digital operator command.
Run command from communication and frequency reference are effective
when multi-function input terminal for this setting is closed (register No.
0001H, 0002
H).
Ru
n command in LOCAL/REMOTE mode and frequency reference are
effective when Open.