Instruction manual

Selecting Stopping Method
Selects the stopping method suitable for application.
Deceleration to stop
Example when accel/decel time 1 is selected
Upon termination of the FWD (REV) run command, the motor decelerates
at the decel rate determined by the time set to deceleration time 1 (n020) and
DC injection braking is applied immediately before stop. DC injection
braking is also applied when the motor decelerates by setting frequency
reference lower than min. output frequency (n016) with FWD (REV) run
command ON. If the decel time is short or the load inertia is large,
overvoltage (OV) fault may occur at deceleration. In this case, increase the
decel time or install a optional braking resistor.
Braking torque :
Without braking resistor : Approx. 20% torque of motor rating
With braking resistor: Approx. 150% torque of motor
rating
70
Selecting stopping method (n005)
SettingSetting
Description
Deceleration to stop
Coast to stop
0
1
OUTPUT
FREQUENCY
ACCEL
TIME 1
(n019)
DECEL
TIME 1
(n020)
DECEL TIME 1
(n020)
MIN. OUTPUT
FREQUENCY
(FREQUENCY AT
DC INJECTION BRAKING
START)
n16
(FACTORY SETTING: 1.5Hz)
DC INJECTION BRAKING
TIME AT STOP (n090)
(FACTORY SETTING: 0.5s)
TIME
FWD (REV)
RUN
COMMAND
ON
*
*
* When frequency reference is changed during running.