Selects processing when STOP key is pressed during operation either from
multi-function input terminal or communications.
69
Operator stop key selection (n007)
Setting
Description
Setting
Description
0
STOP key ineffective when running either from multi-function input
terminals or communications.
1
STOP key effective when running either from multi-function input terminals
or communications. When STOP key is pressed, the inverter stops
according to the setting of constant n005. At this time, the digital operator
displays S P alarm (blinking). This stop command is held in the
inverter until both forward and reverse run commands are open, or
unitl run command from communications becomes zero.
(3) Set carrier frequency selection (n080) to either 1, 2, 3, 4
when using vector control mode. Do not set to 7, 8, or 9.
(4) Carrier frequency is automatically reduced to 2.5kHz when
Reducing carrier frequency selection at low speed ( n175 ) is
set to 1 and the following conditions are satisfied:
Output frequency
5Hz
Output current
110%
Factory setting : 0 ( Disabled )