Instruction manual

68
Factory setting varies according to inverter capacity (kVA).
Voltage Class
(V)
Capacity
(kW)
Initial Setting
Setting
Carrier
Frequency
Maximum Continuous
Output Current
(A)
Reduced Current
(A)
200
Single-phase
3-phase
400
3-phase
0.1
0.25
0.55
1.1
1.5
2.2
4.0
0.37
0.55
1.1
1.5
2.2
3.0
4.0
4
4
4
4
3
3
3
3
3
3
3
3
3
3
10kHz
10kHz
10kHz
10kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
7.5kHz
0.8
1.6
3.0
5.0
8.0
11.0
17.5
1.2
1.8
3.4
4.8
5.5
7.2
9.2
----
7.0
10.0
16.5
1.0
1.6
3.0
4.0
4.8
6.3
8.1
NOTE
(1) Reduce continuous output current when changing carrier
frequency to 4 (10 kHz) for the 200V class (1.5kW or more)
and 400V class inverters. Refer to the table above for the
reduced current.
[Operation Condition]
Input power supply voltage :
3-phase 200 to 230V (200V class)
Single-phase 200 to 240V (200V class)
3-phase 380 to 460V (400V class)
Ambient temperature :
-10 to +50°C (14 to 122°F)
(Protection structure: open chassis
type IP20)
: -10 to +40°C (14 to 105°F)
(Protection structure: top-closed type
IP20, enclosed wall-mounted type
NEMA 1 (TYPE 1))
(2) If the wiring distance is long, reduce the inverter carrier
frequency as described below.
Wiring Distance between
Inverter and Motor
Up to 50m Up to 100m
More than 100m
Carrier frequency
(n080 setting)
10kHz or less
(n080=1,2,3,4,
7,8,9)
5kHz or less
(n080=1,2,
7,8,9)
2.5kHz or less
(n080=1,
7,8,9,)