Instruction manual
65
Analog output AM-AC can be used as a pulse train output
(output frequency monitor, frequency reference monitor).
Set n065 to 1 when using pulse train output.
n065 setting
Constant No.
n065 setting
0
1
Analog monitor output
Pulse monitor output
( Output frequency monitor )
n065
Monitor output type
1 0,1 0
Name Unit Setting range Initial setting
Description
Pulse train signal can be selected by setting n150.
n150 setting Description
0
1
6
12
24
36
40
41
42
43
44
45
1440Hz / Max. frequency (n011)
1F: Output frequency × 1
6F: Output frequency × 6
12F: Output frequency × 12
24F: Output frequency × 24
36F: Output frequency × 36
1440Hz / Max. frequency (n011)
1F: Output frequency × 1
6F: Output frequency × 6
12F: Output frequency × 12
24F: Output frequency × 24
36F: Output frequency × 36
Output frequency
monitor
Frequency reference
monitor
Output frequency
Pulse monitor output
Pulse
Using analog output(AM-AC) as a pulse train signal output (n065)
At the factory setting, the pulse of 1440Hz can be output when output
frequency is 100%.