Instruction manual
10V = 3V
n067 Setting
0.30
·
·
·
Output frequency becomes
100% at this value.
Selects to output either output frequency or output current to analog output
terminals AM-AC for monitoring.
Used to adjust analog output gain.
Set the analog output voltage at 100% of output frequency (output current).
Frequency meter displays 0 to 60Hz at 0 to 3V.
64
Using frequency meter or ammeter (n066)
SettingSetting
Description
Output frequency
Output current
Main circuit DC voltage
Torque monitor
Output power
Output voltage reference
Frequency reference monitor
0
1
2
3
4
5
6
Calibrating frequency meter or ammeter (n067)
AM
AC
0 TO 10VDC
FREQUENCY METER
FM
OUTPUT FREQUENCY
(OUTPUT CURRENT)
Analog monitor gain
can be set by n067
100%
03V
ANALOG OUTPUT
OUTPUT FREQUENCY
(OUTPUT CURRENT)
100%
n067=0.30
n067=1.00
FACTORY SETTING
ANALOG OUTPUT
3V 10V
AM
AC
FREQUENCY METER/AMMETER
(3V 1mA FULL-SCALE)
FM
n067
In initial setting, analog voltage of approx. 10V is output when output
frequency (output current) is 100%.