Instruction manual
Effective when either of output terminal function selections n057, n058 or
n059 are set to “frequency detection” (setting: 4 or 5). “Frequency
detection” turns ON when output frequency is higher or lower than the
setting of frequency detection (n095).
• Frequency detection 1
Output frequency Frequency detection level n095
(Set either of n057, n058 or n059 to “4”.)
60
Frequency detection (n095)
FREQUENCY DETECTION
LEVEL [Hz] (n095)
OUTPUT
FREQUENCY
FREQUENCY
DETECTION
SIGNAL
RELEASE
WIDTH
–2Hz
ON
FREQUENCY
DETECTION
LEVEL (Hz)
(n095)
OUTPUT
FREQUENCY
FREQUENCY
DETECTION
SIGNAL
ONON
RELEASE
WIDTH
+2Hz
• Frequency detection 2
Output frequency Frequency detection level n095
(Set either of n057, n058, n059 to “5”.)