Instruction manual
58
Torque detection
If an excessive load is applied to the machine, output current increase can be
detected to output alarm signals to multi-function output terminals MA, MB,
P1 and P2.
To output an overtorque detection signal, set output terminal function
selection n057 to n059 to “overtorque detection” [ Setting:6 (NO contact) or
7 (NC contact)].
*
Overtorque detection release width (hysterisis) is set at approx. 5% of inverter
rated current.
TIME
n099n099
ONON
MOTOR CURRENT
n098
MULTI-FUNCTION OUTPUT SIGNAL
(OVERTORQUE DETECTION SIGNAL)
TERMINAL MA, MB, P1, P2
**