Instruction manual
52
ON
ONON ON ON
ONON
ON
TIME
(n031) 60.0 Hz
(n030) 55.0 Hz
(n029) 50.0 Hz
(n028) 45.0 Hz
(n027) 40.0 Hz
(n026) 35.0 Hz
(n025) 30.0 Hz
(n024) 25.0 Hz
FREQUENCY
REFERENCE
FWD (REV) RUN/STOP
MULTI-STEP SPEED REF. 1
(TERMINAL S5)
MULTI-STEP SPEED REF. 2
(TERMINAL S6)
MULTI-STEP SPEED REF. 3
(TERMINAL S7)
By inputting a jog command and then a forward (reverse) run command,
operation is enabled at the jog frequency set in n032. When multi-step
speed references 1, 2, 3 or 4 are input simultaneously with the jog
command, the jog command has priority.
Operating at low speed
Constant No.
n032
n050 to n056
Setting
Initial setting : 6.00Hz
Set to “10” for any constant.
Name
Jog frequency
Jog reference
16-Step speed operation
Set frequency reference 9-16 to n120-127.
Set input terminal to multi-step speed reference for multi-function input
selection.