Instruction manual
V/f pattern during vector control
Set V/f pattern as follows during vector control.
The following examples are for 200V class motors. When using 400V
class motors, double the voltage settings (n012, n015, n017).
47
200
11
4.3
13 60
(Hz)
(V)
STANDARD V/F
[MOTOR SPECIFICATION: 60Hz]
200
11
4.3
0.8 2.5
50
(Hz)
(V)
[MOTOR SPECIFICATION: 50Hz]
200
13
5
13
n013
=50Hz
n012
=200V
n011
=90Hz
BASE POINT
60
(Hz)
(V)
HIGH STARTING TORQUE V/F
[MOTOR SPECIFICATION: 60Hz]
200
13
5
0.8 2.5
50
(Hz)
(V)
[MOTOR SPECIFICATION: 50Hz]
CONSTANT TORQUE
CONSTANT OUTPUT OR
VARIABLE OUTPUT
When operating with frequency larger than 60Hz/50Hz, change only
max. output frequency (n011).