Instruction manual

44
Full-range automatic torque boost (when V/f mode is selected; n002=0)
Motor torque requirement changes according to load conditions. Full-
range automatic torque boost adjusts voltage of V/f pattern according to
the requirement. The VS-606V7 automatically adjusts the voltage during
constant-speed operation as well as during acceleration.
The required torque is calculated by the inverter.
This ensures tripless operation and energy-saving effects.
Operation
Normally, no adjustment is necessary for torque compensation gain (n103
factory setting : 1.0). When the wiring distance between the inverter and the
motor is long, or when the motor generates vibration, change the automatic
torque boost gain. In these cases, set the V/f pattern (n011 to n017).
Adjustment of torque compensation time constant (n104) and torque
compensation iron loss (n105) are normally not required.
Adjust torque compensation time constant under the following conditions:
Increase the setting when the motor generates vibration.
Reduce the setting when response is low.
Output voltage Torque compensation gain (n103)
Required torque
f (FREQUENCY)
Required torque Increase voltage
V
(VOLTAGE)