Instruction manual
Simple Data Setting
Digital setting (Refer to 5. OPERATING THE INVERTER) and
potentiometer setting are both available for simple accel/decel operation of
the VS-606V7.
Digital setting is set at the factory (n004=1). For the model with digital
operator (with potentiometer) JVOP-140, factory setting is set by frequency
setting potentiometer (n004=0).
Following is an example in which the function LED’s are used to set
frequency reference, acceleration time, deceleration time, and motor
direction.
40
Operation Steps
Operator
Display
12-LED
Display
Status
Indicator
LED
RUN
ALARM
Status indicator lamp
: ON
: Blinking : OFF
1. Turn the potentiometer fully to the left. Then,
turn the power ON.
2. F/R blinks.
Select FWD/REV run using keys.
Never select REV when reverse run is
prohibited.
3. Press DSPL to blink FREF. Then press RUN.
4.
Operates the motor by turning the
potentiometer to the right. (Frequency
reference corresponds to the potentiometer
position is displayed.)
If the potentiometer is switched rapidly,
the motor also accelerates or decelerate
rapidly corresponding to the
potentiometer movement. Pay attention
to load status and switch the
potentiometer with the speed not to affect
motor
movement.
0.00
FOR
or
REV
0.00 to 60.00
Minimum
output
frequency is
1.50Hz
FREF
RUN
ALARM
RUN
ALARM
NOTE
0.00
RUN
ALARM
F/R
FREF
FREF
NOTE
Data setting by frequency setting potentiometer