Instruction manual
32
Operation Steps
1. Turn ON the power supply.
7. Press to stop.
STOP
Operator
Display
LED
Display
Status Indicator
LED
2. Set constant n004 to 1.
3. Set the following constants.
4. Select forward or reverse run by
pressing qor w key.
5. Set the reference by pressing q or
w key.
6. Press .
15.0
5.0
6.00
1
60.00
0.00➝60.00
FREF
PRGM
FOUT
RUN
ALARM
RUN
ALARM
PRGM
RUN
ALARM
n019 : 15.0 (acceleration time)
n020 : 5.0 (deceleration time)
Examine the application.
(Never select REV when
reverse run is prohibited.)
RUN
FOUT
RUN
ALARM
FREF
RUN
ALARM
RUN
ALARM
RUN
ALARM
F/R
60.00➝0.00
(Forward)
(Reverse)
or
Status indicator lamp : Blinking: Blinking (Long Blinking) : OFF
NOTE
: ON
Selecting rotation direction
It is possible to select the direction in which the motor rotates when the
FORWARD RUN command is executed.
The motor rotates in the opposite direction when the REVERSE RUN
command is executed.
Operation Check Points
▫ Motor rotates smoothly.
▫ Motor rotates in the correct direction.
▫ Motor does not have abnormal vibration or noise.
▫ Acceleration or deceleration is smooth.
▫ Current matching the load flows.
▫ Status indicator LED’s and digital operator display are correct.
n040 Setting
0
1
Description
The motor rotates in the counterclockwise direction as viewed from
the load when the FORWARD RUN command is executed.
The motor rotates in the clockwise direction as viewed from the load
when the FORWARD RUN command is executed.