5. OPERATING THE INVERTER
Initial setting of control mode selection (n002) is set at V/f control mode.
Test Run
The inverter operates by setting the frequency (speed).
There are four types of operation modes for the VS-606V7 :
1 Run command from the digital operator (potentiometer/digital setting).
2 Run command from the control circuit terminal.
3 Run command from communications (MEMOBUS communications).
4 Run command from communication card (optional)
Prior to shipping, the drive is set up to receive run command and frequency
reference from the operator. Below are instructions for running the VS-
606V7 using the digital operator JVOP-147 (without potentiometer). For
instructions on operation, refer to page 40.
Operation reference or frequency reference constants can be selected
separately as shown below.
Name
Run
Command
Selection
Frequency
Reference
Selection
Constant
n003 = 0 --- Enables operator RUN, STOP/RESET
= 1 --- Enables control circuit terminal run/stop
= 2 --- Enables communications (MEMOBUS communications)
= 3 --- Enables communication card (optional)
n004 = 0 --- Enables operator potentiometer
= 1 --- Enables frequency reference 1 (constant n024)
= 2 --- Enables voltage reference (0 to 10V) of control circuit
terminal
= 3 --- Enables current reference (4 to 20mA) of control circuit
terminal
= 4 --- Enables current reference (0 to 20mA) of control circuit
terminal
= 5 --- Enables pulse train reference of control circuit terminal
= 6 --- Enables communications (MEMOBUS communications)
= 7 --- Enables voltage reference (0 to 10V) of operator circuit
terminal
= 8 --- Enables current reference (4 to 20mA) of operator circuit
terminal
= 9 --- Enables communication card (optional)