Instruction manual
Wiring the Control Circuit
Screwdriver blade width
Insert the wire into the lower part of the terminal block and connect it
tightly with a screwdriver.
Wire sheath strip length must be 5.5mm (0.22in.).
29
• Control Circuit terminals
Wiring the control circuit terminals
Only basic insulation is provided for the control circuit terminals.
Additional insulation may be necessary in the end product.
* SW1 can be changed according to sequence input
signal (S1 to S7) polarity.
0V common: NPN side (Initial setting)
+24V common: PNP side
Refer to pages 154 and 155 for SW1.
Refer to pages 80 and 90 for SW2.
Pass the cable through wiring hole and connect. Be sure to mount the covers
on the original position.
12
13
14 22
SW1
SW2
PNP
NPN
OFF
V
ON
1
2
I
1
2
311
MA MB MC
S5
MA MB MC
S6 S7 P1 P2
CONTACT OUTPUT
R R
FS FR FC
S2S1 S3 S4 SC PC
S S
AM
AC RP
0.4 mm max
(0.016 in.)
2.5 mm max
(0.098 in.)
5.5 mm
(0.22 in.)