(10) Voltage drop should be considered when determining wire size.
Voltage drop can be calculated using the following equation:
Phase-to phase voltage drop (V)
= 3 wire resistance (/km) × wiring distance (m) × current (A) × 10
-3
Select a wire size so that voltage drop will be less than 2% of the
normal rated voltage.
Wire and Terminal Screw Sizes
Model
Common to
all models
Terminal Symbol
MA, MB, MC
S1 to S7,P1,P2,SC,PC,R+,R-
S+,S-,FS,FR,FC,AM,AC,RP
Screw
twisted wire
single
mm
2
mm
2
Wire
Recommended size
Applicable size
Applicable size
Recommended size
AWGAWG
0.5 to 1.25
0.5 to 1.25
twisted wire
single
0.5 to 0.75
0.5 to 1.25
20 to 16
20 to 16
20 to 18
20 to 16
Shielded
wire or
equivalent
1. Control Circuit
Model
Terminal
Symbol
Screw
2. Main Circuit
R/L1,S/L2,T/L3,
–,+1,+2,B1,B2,
U/T1,V/T2,W/T3
0.8 to 1.0
(7.1 to 8.88)
0.8 to 1.0
(7.1 to 8.88)
0.8 to 1.0
(7.1 to 8.88)
0.8 to 1.0
(7.1 to 8.88)
1.2 to 1.5
(10.65 to 13.31)
0.75 to 2
0.75 to 2
0.75 to 2
0.75 to 2
2 to 5.5
18 to 14
18 to 14
18 to 14
18 to 14
14 to 10
2
2
2
2
14
14
14
14
600V
vinyl-
sheathed
wire or
equivalent
200V Class 3-phase Input Series
Note : The wire size is set for copper wires at 75°C (160°F).
Tightening
Torque
N
m (Ib
in
)
Tightening Torque
N m (Ib in)
M3
M2
Type
mm
2
Wire
AWG
mm
2
AWG
Type
0.5 to 0.6
(4.44 to 5.33)
0.22 to 0.25
(1.94 to 2.21)
0.75
0.75
18
18
5.5
10
CIMR-
V7
*
C
20P1
R/L1,S/L2,T/L3,
–,+1,+2,B1,B2,
U/T1,V/T2,W/T3
CIMR-
V7
*
C
20P2
R/L1,S/L2,T/L3,
–,+1,+2,B1,B2,
U/T1,V/T2,W/T3
CIMR-
V7
*
C
20P4
R/L1,S/L2,T/L3,
–,+1,+2,B1,B2,
U/T1,V/T2,W/T3
CIMR-
V7
*
C
20P7
R/L1,S/L2,T/L3,
–,+1,+2,B1,B2,
U/T1,V/T2,W/T3
CIMR-
V7
*
C
24P0
M3.5
M3.5
M3.5
M3.5
M4
1.2 to 1.5
(10.65 to 13.31)
2 to 5.5 14 to 10
3.5
12
R/L1,S/L2,T/L3,
–,+1,+2,B1,B2,
U/T1,V/T2,W/T3
CIMR-
V7
*
C
22P2
M4
1.2 to 1.5
(10.65 to 13.31)
2 to 5.5 14 to 10
2
14
3.5
12
R/L1,S/L2,T/L3,
–,+1,+2,B1,B2,
U/T1,V/T2,W/T3
CIMR-
V7
*
C
21P5
M4