Instruction manual

170
No.
< 400V class 3-phase
Name Unit
Inverter capacity kW 0.37kW 0.55kW 1.1kW 1.5kW 2.2kW 4.0kW
n036 Motor rated current A 0.6 1.0 1.6 3.1 4.2 7.0
n105
Torque compensation
iron loss
W 3.4 4.0 6.1 11.0 11.7 19.3
n106 Motor rated slip Hz 2.5 2.7 2.6 2.5 3.0 3.2
n107
Line to neutral
(per phase)*
41.97 19.08 11.22 5.044 3.244 1.514
n108
Motor leakage inductance
MH 224.3 168.8 80.76 53.25 40.03 24.84
n110 Motor no-load current % 73 63 52 45 35
3.0kW
7.0
19.3
3.2
1.514
24.84
33 33
* Sets the value of the motor resistance for one phase.