Instruction manual

Terminal Description
153
Type Terminal Name Function (Signal Level)
Main Circuit
Control Circuit
InputOutput
Sequence
Frequency
reference
Multi-function
contact output
Communication
Circuit Terminal
MEMOBUS
communications
R/L1,
S/L2,
T/L3
U/T1,
V/T2,
W/T3
B1, B2
+2, +1
+1,
S1
AM
AC
R+
S-
S+
R-
AC power supply
input
Inverter output
Braking resistor
connection
DC reactor
connection
DC power supply input
Grounding
NO contact output
NC contact output
Contact output common
Photo-coupler output 1
Photo-coupler output 2
Photo-coupler output common
Analog monitor common
Analog monitor output
Communications
input (+)
Communications
output ()
Communications
output (+)
Communications
input ()
Inverter output
Use main circuit power input.
(Use terminals R/L1 and S/L2 for single-phase
inverters. Never use terminal T/L3.)
Braking resistor connection
When connecting optional DC reactor, remove the
main circuit short-circuit bar between +2 and +1.
For grounding (according to the local grounding
code)
DC power supply input (+1: positive -: negative) *
Factory setting: Fault reset
Factory setting: External fault
(NO contact)
Factory setting closed: REV run
open: FWD run
Factory setting closed: FWD run
open: REV run
Factory setting: fault
Factory setting:
Output frequency 0 to +10V
MEMOBUS communication
Run through RS-485 or
RS-422.
Factory setting:
Run
Factory setting:
Frequency agreed
0V
0V
Photo-coupler
insulation,
24VDC,
8mA
Contact capacity
250VAC 1A or less,
30VDC 1A or less
Photo-coupler output
+48VDC, 50mA or
less
0 to +10VDC, 2mA or
less, 8-bit
resolution
RS-485/422
MEMOBUS protocol,
19.2 kps max.
0V
Factory setting: Jog reference
Factory setting: Multi-step speed
reference 2
Factory setting: Multi-step speed
reference 1
For control signal
33kHz max.
+12V (permissible current 20mA max.)
MA
MB
MC
P1
P2
PC
SC
S7
S6
S5
S4
S3
S2
RP
FS
Frequency reference
common
FR
FC
Multi-function input
selection common
Multi-function input
selection 7
Multi-function input
selection 6
Multi-function input
selection 5
Multi-function input
selection 4
Multi-function input
selection 3
Multi-function input
selection 2
Multi-function input
selection 1
Master speed reference
pulse train input
Master speed
frequency reference
Power for frequency
setting
0 to +10VDC (20k) or 4 to 20mA (250k) or
0 to 20mA (250) (1/1000 resolution)
* DC power supply input terminal is not applied to CE/UL standards.
Can be swiched to pulse monitor output.
Minimum permissible load: 5VDC, 10mA (as reference value)