9. SPECIFICATIONS
Standard Specifications (200V Class)
145
200V single- / 3-phase
Voltage Class
Inverter Capacity(kVA)
Control Method
Overload Capacity
Accel/Decel Time
Braking Torque
V/f Characteristics
Rated Output
Current(A)
Max. Output
Frequency(Hz)
Rated Input Voltage
and Frequency
Allowable Voltage
Fluctuation
Allowable Frequency
Fluctuation
Frequency Control
Range
Frequency Setting
Resolution
Frequency Reference
Signal
Output Frequency
Resolution
Frequency Accuracy
(Temperature Change)
Max. Output Voltage(V)
3-phase, 200 to 230V (proportional to input voltage)
Single-phase, 200 to 240V (proportional to input voltage)
3-phase, 200 to 230V, 50/60Hz
Single-phase, 200 to 240V, 50/60Hz
Digital reference: ± 0.01% (-10 to + 50°C)
Analog reference: ± 0.5% (25 ± 10°C)
0 to 10VDC (20kΩ), 4 to 20mA (250Ω), 0 to 20mA (250Ω)
pulse train input, frequency setting potentiometer (Selectable)
Digital reference:
0.01Hz (less than 100Hz) / 0.1Hz (100Hz or more)
Analog reference: 1 / 1000 of max. output frequency
400Hz(Programmable)
-15 to + 10%
Sine wave PWM (V/f control/vector control selectable)
0.1 to 400Hz
0.01Hz
150% rated output current for one minute
Possible to program any V / f patterm
Short-term average deceleration torque †
0.1, 0.25kW (0.13HP, 0.25HP): 150%
0.55, 1.1kW (0.5HP, 1HP): 100%
1.5kW (2HP) : 50%
2.2kW(3HP) or more: 20%
Continuous regenerative torgue: Approx. 20% (150% with
optional braking resistor, braking transistor built-in)
0.00 to 6000 sec.
(accel / decel time are independently programmed)
Output
Characteristics
Power
Supply
Control Characteristics
±5%
Max. Applicable Motor Output
kW
∗
Model
CIMR-V7
*
C????
3-
phase
20P1
B0P1
0.1
0.3
0.8
20P2
B0P2
0.25
0.6
1.6
20P4
B0P4
0.55
1.1
3
20P7
B0P7
1.1
1.9
5
21P5
B1P5
1.5 2.2 4.0
3.0
8
22P2
B2P2
4.2
11
24P0
B4P0
6.7
17.5
Single-
phase
*
Based on a standard 4-pole motor for max. applicable motor output.
† Shows deceleration torque for uncoupled motor decelerating from 60Hz with the shortest
possible deceleration time.