Instruction manual

127
Using Inverters for Elevating Machines
When using the VS-606V7 for elevating machines such as elevators and
cranes, make sure that the brake holds and observe the following
precautions for safe operation.
Brake ON/OFF Sequence
For the holding brake's ON/OFF sequence, use the following inverter
output signals according to the set control mode.
Do not use "Running (Set value: 1)" for the holding brake's ON/OFF
interlock signal.
Notes: 1. For Vector control (n002=1), use the same brake ON/OFF sequence with the
same signals as for V/F control.
2. Shows the setting when a multi-function photocoupler output terminal (P1-PC) is
used.
3. Usually, make the following settings for the frequency detection (n095):
For V/f control: Motor rated slip frequency + 1 Hz
For Vector control: 2.5 Hz to 3.0 Hz
If the set value is too low, the motor torque is insufficient and the load may shift
when the brake is applied. Be sure to set n095 to a value larger than that of the
minimum output frequency (n016)and larger than that of the brake releasing
width shown in the following figure. If the set value is too large, the motor may
not run smoothly when it starts running.
NOTE
Control Mode
Brake ON/OFF Signal
Brake ON/OFF Level Adjustment
V/f Control
(Note 1)
(n002=0)
Frequency
detection 1
n058=4
Frequency
detection level
n095=2.50 Hz
to 4.00 Hz
(Note 3)
Signal Name
Constant
(Note 2)
ConstantSignal Name
Output freqency n095
Freqency detection level 1
Time
Releasing width -2Hz
ON
OFF