Instruction manual

122
Constant
n035
Setting
40
to
3999
Description
0
1
2
3
(Example) To display 20.0 at 100 % of frequency reference, set n035 to 1200.
Setting range
min{(Lower 3-digits of n035)
Frequency reference lower limit (n034) to (Lower 3-d igits
of n035)
Frequency reference upper limit (n033), 400Hz (Lower 3-digits of n035)
Fmax(n011), 999}
Max. upper limit value: (Set value
(Lower 3-digits of n035)) Fmax(n011) 400 Hz
Notes:
1.
The frequency reference constants and monitor display data for which this selection of
unit function is valid, are stored in the inverter in units of Hz.
The units are converted as follows.
Setting/Display Constant n035 Frequency reference constants
Data for monitor display
2. The upper limit for each unit is the figure whose fractions below the significant
digits are cut off.
(Example) Where the upper limit value for the unit Hz is 60.00 Hz and n035 = 39,
120
60.00 Hz 39 = 184.9, accordingly 184 r/min is displayed for
the upper limit value.
For the displays other than upper limit value, the fractions below the significant
digits are rounded.
3. To execute VERIFY for constant COPY function, frequency reference constants
(in units of Hz) is applied.
Each unit
system
Units of Hz
Display
Setting
0.
By a number of 4th digit of n035, set the position of decimal point.
By 1st to 4th digit of n035, set a 3-digits figure excluding decimal point.
Number of 4th digit. Position of decimal point
40 to 3999
Set the display value at 100% of frequency reference (set value of Fmax(n011))
at 1st to 4th digit of n035.
.
.