Instruction manual

A setting range check and matching check for the written-in constants are
executed after the constants are written from the digital operator to the
inverter. If any constant error is found, the written constants are discarded
and the constants stored before writing are restored.
When a setting range error is found, the constant No. where an error occurs
is indicated by blinking.
When a matching error is found, OP ? (?:a number) is indicated by
blinking.
116
Explanation Operator display
Enable the settings for the
constants n001 to n179.
Execute write-in (COPY) by
Constant Copy Function
Selection (n176).
Press DSPL to light [PRGM]
Press ENTER to display the set
value.
Change the set value to 4 by
pressing or key.
Press ENTER.
Change the constant No. to n176
by pressing or key.
Press ENTER to display the set
value.
Change the set value to CPy by
pressing or key.
Press ENTER.
Perss DSPL or ENTER.
N001
(Can be a different constant No.)
1 (Lit)
(Can be a different set value.)
4 (Blinks)
4 (Lit for one second)
N001 (The constant No. is
displayed)
N176
DY (Lit)
CPY (Lit)
CPY
(Blinks while executing CPY)
END (End is displayed when the
execution of CPY is completed.)
N176 (The constant No. is
displayed)
[ Example ] Write the constants from EEROM inside the degital operator to the inverter
v
v
v
v
v