Instruction manual

Writes the constants stored inside the digital operator in batch to the
inverter. Write-in is possible only for the inverters with same product series,
power supply specifications and control mode (V/f control or vector
control).
Therefore, writing from 200 V class to 400 V class (or vice versa), from V/f
control mode to vector control mode (or vice versa), and from VS-606V7 to
VSmini J7 are not possible.
Constant Copy Function Selection (n176), Constant Read Selection Prohibit
(n177), Fault history (n178), Software version No. (n179), and hold output
frequency is not written vAE will appear (blinking) when the capacity of the
inverters differs.
Press ENTER to continue writing in (the COPY function).
Press STOP/RESET to stop the COPY function.
Following constants are not written if the inverter capacity is different.
Constants added with software version upgrades will not be written between
VS-606V7 Inverters without the additional constants and VS-606V7
Inverters with the additional constants.
For this reason, the settings for the additional constants will not be changed
by the copy operation.
115
Constant No. Name Constant No. Name
n011 to n017 V/ f setting n108
Motor leakage inductance
n080
Carrier frequency selection
n110
Motor no-load current
n106 Motor rated slip n158
Motor code
n036 Motor rated current n109
Torque compensation
voltage limiter
n105 Torque compensation
iron loss
n107
Line to neutral (per phase)
n140
Energy-saving coefficient
K2
COPY function