Instruction manual

114
Reads out the constants in batch from the inverter and stores them in
EEPROM inside the digital operator. When the read-out is executed, the
previously stored constants data in the EEPROM are cleared and replaced
with the newly entered constants.
Explanation Operator display
[Example] Store the constants read out from the inverter, in the EEPROM inside the digital operator.
Enable the setting of the
constants n001 to n179.
Set contant read prohibited
selection (n177) to READ
enabled. 1
Execute read-out (READ) by
constant copy Function
selection (n176).
Set Constant read prohibited
selection (n177) to READ
disabled. 2
Press DSPL to light [PRGM].
Press ENTER to display the
set value.
Change the set value to 4 by
pressing or key.
Press ENTER.
Change the constant No. to
n177 by pressing or key.
Press ENTER to display the
set value.
Change the set value to 1 by
pressing or key.
Press ENTER.
Change the constant No. by
pressing or key.
Press ENTER to display the
set value.
Change the set value to rEd
by pressing or key.
Press ENTER.
Press DSPL or ENTER
Change the constant No.to
N177 by pressing or key.
Press ENTER to display the
set value.
Chage the set value to 0 by
pressing or key.
Press ENTER.
001
(Can be a different constant No.)
1 ( Lit )
(Can be a different set value.)
4 (Blinks)
4 (Lit for one second.)
N001 (The constant is displayd.)
N177
0 (Lit)
1 (Blinks)
1 (Lit for one second)
N177 (The constant displayed.)
N176
ED (Lit)
ED (Lit)
ED (Blinks while executing
READ)
END (End is displayed after the
execution of READ is completed.)
N176 (The constant is
displayed.)
N177
1 (Lit)
0 (Blinks)
0 (Lit for one second)
N177 (
the constant No. is
display
ed.)
1 When READ is enabled (n177=1), this setting is not necessary.
2
The setting is not necessary unless the READ prohibition is selected.
v
v
v
v
v
v
v
v
v
v
v
v
v
v
READ function