Instruction manual

100
Carry out the self-test in the following procedure.
1. Turn ON the VS-606V7 power supply. Set constant n056 to 35 (self-test).
2. Turn OFF the VS-606V7 power supply.
3. Make the following wiring with the power supply turned OFF.
4. Turn the power ON.
Normal operation: Operator displays frequency reference value.
Faulty operation: Operator displays CE, fault signal is turned ON and
inverter ready signal is turned OFF.
S 7 P 1 P 2 R + R
-
S 4 S C P C S + S
-
(Note: Select NPN side for SW1.)
Performing self-test
VS-606V7 is provided with a function to perform self-diagnosis for oper-
ation check of the serial communication I/F circuit. This function is
called self-test. In the self-test, connect the sending terminal with the
receiving terminal in the communication section. It assures if the data
received by VS-606V7 is not being changed. It also checks if the data
can be received normally.