Instruction manual
10. Specifications
249
142 018E Energy-saving Control
Voltage Lower Limit at
6Hz
0% to 25% 1% 12% 175
143 018F Power Average Time 1 to 200 1 = 24 ms 1 (24 ms) 176
144 0190 Search Operation Volt-
age Limit
0% to
100%
1% 0% 176
145 0191 Search Operation Volt-
age Step at 100%
0.1% to
100%
0.1% 0.5% 176
146 0192 Search Operation Volt-
age Step at 100%
0.1% to
10.0%
0.1% 0.2% 176
148 0194 DeviceNet I/O Produced
Connection Path
020 to 156 - 021 ---
149 0195 DeviceNet I/O Con-
sumed Connection Path
020 to 106 - 63 ---
150 0196 MAC ID Setting 0 to 63 1 0 ---
151 0197 DeviceNet Timeover De-
tection Selection
0 to 4 1 0 ---
152 0198 Baud Rate Setting 0 to 2 1 0 ---
153 0199 DeviceNet Speed Scale −15 to 15 1 0 ---
154 019A DeviceNet Current Scale −15 to 15 1 0 ---
155 019B DeviceNet Power Scale −15 to 15 1 0 ---
156 019C DeviceNet Voltage Scale −15 to 15 1 0 ---
157 019D DeviceNet Time Scale −15 to 15 1 0 ---
158 019E Motor Code (Energy-
saving Control)
0 to 70 1 (Note 7) 174
159 019F Upper Voltage Limit for
Energy-saving Control at
60 Hz
0% to
120%
1% 120% 175
160 01A0 Upper Voltage Limit for
Energy-saving Control at
6 Hz
0% to 25% 1% 16% 175
161 01A1 Search Operation Pow-
er Detection Hold Width
0% to
100%
1% 10% 177
162 01A2 Time Constant of Power
Detection Filter
0 to 255 1 = 4 ms 5 (20 ms) 177
163 01A3 PID Output Gain 0.0 to 25.0 0.1 1.0 182
164 01A4 PID Feedback Value Se-
lection
0 to 5 1 0 180
166 01A6 Input Open-phase De-
tection Level
0% to
100%
1% 0% ---
167 01A7 Input Open-phase De-
tection Time
0 to 255 s 1 s 0 s ---
168 01A8 Output Open-phase De-
tection Level
0% to
100%
1% 0% ---
No. Register
No. for
Trans-
mission
Name Setting
Range
Setting Unit Factory
Setting
User
Setting
Ref.
Page