Instruction manual

10. Specifications
247
104 0168 Torque Compensation
Time Constant
0.0 to
25.5 s
0.1 s 0.3 s
(Note 8)
131
105 0169 Torque Compensation
Iron Loss
0.0 to 6550 0.01 W (less
than 1000 W)/
1 W (1000 W
or more)
(Note 3) 131
106 016A Motor Rated Slip 0.0 to
20.0 Hz
0.1 Hz (Note 3) 132
107 016B Line to Neutral (per
Phase)
0.000 to
65.50
0.001 (less
than 10 )/
0.01 (10
or more)
(Note 3) 132
108 016C Motor Leakage Induc-
tance
0.00 to
655.0 mH
0.01 mH (less
than 100 mH)/
0.1 mH
(100 mH or
more)
(Note 3) 134
109 016D Torque Compensation
Voltage Limiter
0% to
250%
1% 150% ---
110 016E Motor No-load Current 0% to 99% 1% (Note 3) 132
111 016F Slip Compensation Gain 0.0 to 2.5 0.1 0.0 (Note 8) 171
112 0170 Slip Compensation Time
Constant
0.0 to
25.5 s
0.1 s 2.0 s
(Note 8)
171
113 0171 Slip Correction During
Regenerative Operation
0, 1 1 0 133
115 0173 Stall Prevention Auto-
matic Decrease Selec-
tion
0, 1 1 0 169
116 0174 Acceleration/decelera-
tion Time during Stall
Prevention
0, 1 1 0 170
117 0175 Undertorque Detection
Function Selection
0 to 4 1 0 ---
118 0176 Undertorque Detection
Level
0% to
200%
1% 10% ---
119 0177 Undertorque Detection
Time
0.1 to
10.0 s
0.1 s 0.1 s ---
No. Register
No. for
Trans-
mission
Name Setting
Range
Setting Unit Factory
Setting
User
Setting
Ref.
Page