Instruction manual

242
Constants List
• Constants That Can Be Changed during Operation
The constants whose numbers are shaded can be changed during
operation.
First Functions (Constants n001 to n044)
No. Register
No. for
Trans-
mission
Name Setting
Range
Setting Unit Factory
Setting
User
Setting
Ref.
Page
001 0101H Constant Selection/Ini-
tialization
0 to 4, 6,
8, 9
1 1 127
002 0102 Control Mode Selection
(Note 6)
0, 1 1 0
(Note 1)
(Note 6)
132
003 0103 RUN Command Selec-
tion
0 to 3 1 3 137
004 0104 Frequency Reference
Selection
0 to 9 1 9 138
005 0105 Stopping Method Selec-
tion
0, 1 1 0 155
006 0106 Reverse Run Prohibit 0, 1 1 0 139
007 0107 Stop Key Selection 0, 1 1 0 154
008 0108 Frequency Reference
Selection in Local Mode
0, 1 1 1
(Note 5)
137
009 0109 Frequency Reference
Setting Method From
Digital Operator
0, 1 1 0 138
010 010A Detecting Fault Contact
Of Digital Operator
0, 1 1 0 137
011 010B Max. Output Frequency 50.0 to
400.0 Hz
0.1 Hz 50.0 Hz 129
012 010C Max. Voltage 0.1 to
255.0 V
(0.2 to
510.0)
0.1 V 200.0 V
(Note 2)
129
013 010D Max. Voltage Output
Frequency (Base Fre-
quency)
0.2 to
400.0 Hz
0.1 Hz 50.0 Hz 129
014 010E Mid. Output Frequency 0.1 to
399.9 Hz
0.1 Hz 1.5 Hz
(Note 8)
129
015 010F Mid. Output Frequency
Voltage
0.1 to
255.0 V
0.1 V 12.0 V
(Note 2)
(Note 8)
129
016 0110 Min. Output Frequency 0.1 to
10.0 Hz
0.1 Hz 1.5 Hz
(Note 8)
129
017 0111 Min. Output Frequency
Voltage
0.1 to
50.0 V
(Note 2)
0.1 V 12.0 V
(Note 2)
(Note 8)
129