Voltage Class 200 V single-/3-phase
Model
CIMR-
V7
*1
C

3-
phase
20P1 20P2 20P4 20P7 21P5 22P2 23P7 25P5 27P5
Single-
phase
B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B3P7 - -
Motor Over-
load Protec-
tion
Electronic thermal overload relay
Instanta-
neous
Overcurrent
Motor coasts to a stop at approx. 250% of Inverter rated current
Overload Motor coasts to a stop after 1 minute at 150% of Inverter rated output cur-
rent
Overvoltage Motor coasts to a stop if DC bus voltage exceed 410 V
Undervoltage Stops when DC bus voltage is approx. 200 V or less (approx. 160 V or
less for single-phase series).
Momentary
Power Loss
Following items are selectable: Not provided (stops if power loss is 15 ms
or longer), continuous operation if power loss is approx. 0.5 s or shorter,
continuous operation.
Heatsink
Overheat
Protected by electronic circuit.
Stall Preven-
tion Level
Can be set individual level during acceleration/deceleration, provided/not
provided available during coast to a stop.
Cooling Fan
Fault
Protected by electronic circuit (fan lock detection).
Ground Fault Protected by electronic circuit (overcurrent level).
Power
Charge Indi-
cation
ON until the DC bus voltage becomes 50 V or less. RUN indicator stays
ON or Digital Operator indicator stays ON.
Multi-
func-
tion
Input
Seven of the following input signals are selectable: Forward/reverse run
(3-wire sequence), fault reset, external fault (MA contact input), multi-step
speed operation, JOG command, acceleration/deceleration time select,
external baseblock (MA contact input), SPEED SEARCH command, AC-
CELERATION/DECELERATION HOLD command, LOCAL/REMOTE se-
lection, communication/control circuit terminal selection, emergency stop
fault, emergency stop alarm, UP/DOWN command, PID control cancel,
PID integral reset/hold
Multi-
func-
tion
Output
Following output signals are selectable (1 MA contact output (See note
3.), 2 photocoupler outputs):
Fault, running, zero speed, frequency agree, frequency detection (output
frequency or set value), overtorque detection, undervoltage detection,
minor error, baseblock, operating mode, Inverter run ready, fault retry, UV,
speed search, PID feedback loss detection
Standard
Functions
Voltage vector control, full-range automatic torque boost, slip compensa-
tion, DC injection braking current/time at startup/stop frequency reference
bias/gain, PID control, energy-saving control, constant copy, frequency
reference with built-in potentiometer, unit selection for frequency refer-
ence setting/display
Protective FunctionsOutput Functions
Input SignalsOutput Signals