7. Programming Features
161
Time Chart for UP/DOWN Command Input
Note: 1. When UP/DOWN commands are selected, the upper limit speed is set
regardless of frequency reference.
Upper limit speed =Maximum Output Frequency (n011)
× Frequency Reference Upper Limit (n033)/100
2. Lower limit value is either the Minimum Output Frequency (n016) or
the frequency Reference Lower Limit (n034) (whichever is larger.).
3. When the FWD (REV) RUN command is input, operation starts at the
lower limit speed without using the UP/DOWN commands.
4. If the JOG command is input while running for an UP/DOWN com-
mand, the JOG command has priority.
5. Multi-step speed references 1 to 4 are not effective when an UP/
DOWN command is selected. Multi-step speed references are effec-
tive while running in hold status.
6. When 1 is set for the HOLD Output Frequency Memory Selection
(n100), the output frequency can be recorded during HOLD.
FWD RUN
UP command S3
DOWN command S4
Upper limit speed
Lower limit speed
output frequency
FREQUENCY agree
signal
U = UP (accelerating) status
D = DOWN (decelerating) status
H = HOLD (constant speed) status
U1 = UP status, clamping at upper limit speed
D1 = DOWN status, clamping at lower limit speed